If you are unable to configure Kaspersky IoT Secure Gateway 100 and cannot find a resolution to your issue in the documentation, you can run diagnostics yourself and then contact Technical Support with the diagnostic information that you obtained.
The Kaspersky IoT Secure Gateway 100 diagnostics scenario consists of the following steps:
Perform the following checks on the MQTT broker side:
Conduct an inspection of hardware components. You will need to assess the following:
Connect to the gateway via USB-UART adapter and use PuTTY to obtain a diagnostics log. In the obtained diagnostics log, check the following:
OPC UA Client has established connection
message;MQTT Publisher established connection
message;If you encounter errors establishing a secure connection, you should first verify that the date and time are set correctly. If the date and time are correctly set on the gateway but a certificate validation error occurs, you should check the format and validity dates of the certificates and make sure that the important fields have been completed correctly.
To search for errors, you can also use the health log files stored on the microSD memory card.
If you are not able to restore the correct operation of the gateway on your own, please contact Technical Support by emailing your query to support@aprotech.ru.
Please attach the following to your query:
dhcpcd.conf
files);OpcUaClientSettings-0.json
file);MqttPublisherSettings-0.json
file);